Tuesday, 4 August 2015

CT- CURRENT TRANSFORMER

A current transformer (CT) is used for measurement of alternating electric currents. Current transformers, together with voltage (or potential) transformers (VT or PT), are known as instrument transformers. When current in a circuit is too high to apply directly to measuring instruments, a current transformer produces a reduced current accurately proportional to the current in the circuit, which can be conveniently connected to measuring and recording instruments. A current transformer isolates the measuring instruments from what may be very high voltage in the monitored circuit. Current transformers are commonly used in metering and protective relays in the electrical power industry.

Current Transformer Burden

Burden is the load imposed on the secondary of the CT at rated current and is measured in VA (product of volts and amps). The accuracy class applies only to loads at rated VA and below, down to one quarter VA .
The burden on the secondary of a CT includes the effect of pilot leads, connections etc , as well as the instrument burden itself.
In situations where the meter is remote from the current transformer, the resistance of the pilot wires may exceed the meter impedance many times in these cases it is often economical to use 1 amp meters and CTs. 
Instrument TypeApproximate Burden
Ammeter0.5 - 5VA
Voltmeter2 - 5VA
Frequesncy Meter1 - 5VA
Protection Relay0.2 - 30VA
The diagram below shows the burden imposed on the CT due to a run of pilot wire. It will be seen that a pilot loop of 2.5mm2 wire, 60 metres long (30 metres distance) has a load of 12.5 VA on a 5 amp CT but only 0.5VA on a 1 amp CT.
Lead -Burden -Chart

CT Ratio

Current transformers where the secondary current under normal operation is practically proportional to the primary current. e.g 3000/1A would be 3000A primary (input) with 1A secondary (output) which in effect would be 3000 turns of copper around the steel with winding wire or 3000:1 proportional ratio.
In the case of 3000/5A again the primary would be 3000A with a 5A secondary, however as the ratio is proportional  primary to secondary there would be only 600 turns of winding wire or 600:1 proportional ratio.

CT Accuracy Class or Current Transformer Class

A CT is similar to a electrical power transformer to some extent, but there are some difference in construction and operation principle. For metering and indication purpose, accuracy of ratio, between primary and secondary currents are essential within normal working range. Normally accuracy of current transformer required up to 125% of rated current; as because allowable system current must be below 125% of rated current. Rather it is desirable the CT core to be saturated after this limit since the unnecessary electrical stresses due to system over current can be prevented from the metering instrument connected to the secondary of the CT as secondary current does not go above a desired limit even primary current of the CT rises to a very high value than its ratings. So accuracy within working range is main criteria of a CT used for metering purpose. The degree of accuracy of a metering CT is expressed by CT accuracy class or simply current transformer class or CT class.

Tuesday, 28 July 2015

Surge arrester

A surge arrester is a device to protect electrical equipment from over-voltage transients caused by external (lightning) or internal (switching) events. Also called a surge protection device (SPD) or transient voltage surge suppressor (TVSS), this class of device is used to protect equipment in power transmission and distribution systems. (For consumer equipment protection, different products calledsurge protectors are used.)
To protect a unit of equipment from transients occurring on an attached conductor, a surge arrester is connected to the conductor just before it enters the equipment. The surge arrester is also connected to ground and functions by routing energy from an over-voltage transient to ground if one occurs, while isolating the conductor from ground at normal operating voltages. This is usually achieved through use of a varistor, which has substantially different resistances at different voltages.
Surge arresters are not generally designed to protect against a direct lightning strike to a conductor, but rather against electrical transients resulting from lightning strikes occurring in the vicinity of the conductor. Lightning which strikes the earth results in ground currents which can pass over buried conductors and induce a transient that propagates outward towards the ends of the conductor. The same kind of induction happens in overhead and above ground conductors which experience the passing energy of an atmospheric EMP caused by the lightning flash. Surge arresters only protect against induced transients characteristic of a lightning discharge's rapid rise-time and will not protect against electrification caused by a direct strike to the conductor. Transients similar to lightning-induced, such as from a high voltage system's fault switching, may also be safely diverted to ground; however, continuous overcurrents are not protected against by these devices. The energy in a handled transient is substantially less than that of a lightning discharge; however it is still of sufficient quantity to cause equipment damage and often requires protection.
Without very thick insulation, which is generally cost prohibitive, most conductors running more than a minimal distance, say greater than about 50 feet, will experience lightning-induced transients at some time during use. Because the transient is usually initiated at some point between the two ends of the conductor, most applications install a surge arrester just before the conductor lands in each piece of equipment to be protected. Each conductor must be protected, as each will have its own transient induced, and each SPD must provide a pathway to earth to safely divert the transient away from the protected component. The one notable exception where they are not installed at both ends is in high voltage distribution systems. In general, the induced voltage is not sufficient to do damage at the electric generation end of the lines; however, installation at the service entrance to a building is key to protecting downstream products that are not as robust.

Types[edit]

  • Low-voltage surge arrester: Apply in Low-voltage distribution system, exchange of electrical appliances protector, low-voltage distribution transformer windings
  • Distribution arrester: Apply in 3KV, 6KV, 10KV AC power distribution system to protect distribution transformers, cables and power station equipment
  • The station type of common valve arrester: Used to protect the 3 ~ 220KV transformer station equipment and communication system
  • Magnetic blow valve station arrester: Use to 35 ~ 500KV protect communication systems, transformers and other equipment
  • Protection of rotating machine using magnetic blow valve arrester: Used to protect the AC generator and motor insulation
  • Line Magnetic blow valve arrester: Used to protect 330KV and above communication system circuit equipment insulation
  • DC or blowing valve-type arrester: Use to protect the DC system’s insulation of electrical equipment
  • Neutral protection arrester: Apply in motor or the transformer’s neutral protection
  • Fiber-tube arrester: Apply in the power station’s wires and the weaknesses protection in the insulated
  • Plug-in Signal Arrester: Used to twisted-pair transmission line in order to protect communications and computer systems
  • High-frequency feeder arrester: Used to protect the microwave, mobile base stations satellite receiver, etc.
  • Receptacle-type surge arrester: Use to Protect the terminal Electronic equipment
  • Signal Arrester: Apply in MODEM, DDN line, fax, phone, process control signal circuit etc.
  • Network arrester: Apply in servers, workstations, interfaces etc.
  • Coaxial cable lightning arrester: Used on the coaxial cable to protect the wireless transmission and receiving system

Tuesday, 5 May 2015

Types of Electrical Insulator | Overhead Insulator

There are mainly three types of insulator used as overhead insulator likewise
1. Pin Insulator 2. Suspension Insulator 3. Strain Insulator In addition to that there are other two types of electrical insulator available mainly for low voltage application, e.i. Stay Insulator and Shackle Insulator.

Pin Insulator

Pin Insulator is earliest developed overhead insulator, but still popularly used in power network up to 33KV system. Pin type insulator can be one part, two parts or three parts type, depending upon application voltage. In 11KV system we generally use one part type insulator where whole pin insulator is one piece of properly shaped porcelain or glass. As the leakage path of insulator is through its surface, it is desirable to increase the vertical length of the insulator surface area for lengthening leakage path. In order to obtain lengthy leakage path, one, tow or more rain sheds or petticoats are provided on the insulator body. In addition to that rain shed or petticoats on an insulator serve another purpose. These rain sheds or petticoats are so designed, that during raining the outer surface of the rain shed becomes wet but the inner surface remains dry and non-conductive. So there will be discontinuations of conducting path through the wet pin insulator surface. In higher voltage like 33KV and 66KV manufacturing of one part porcelain pin insulator becomes difficult. Because in higher voltage, the thickness of the insulator become more and a quite thick single piece porcelain insulator can not manufactured practically. In this case we use multiple part pin insulator, where a number of properly designed porcelain shells are fixed together by Portland cement to form one complete insulator unit. For 33KV tow parts and for 66KV three parts pin insulator are generally used. pin insulator

Designing Consideration of Electrical Insulator

The live conductor attached to the top of the pin insulator is at a potential and bottom of the insulator fixed to supporting structure of earth potential. The insulator has to withstand the potential stresses between conductor and earth. The shortest distance between conductor and earth, surrounding the insulator body, along which electrical discharge may take place through air, is known as flash over distance. 1. When insulator is wet, its outer surface becomes almost conducting. Hence the flash over distance of insulator is decreased. The design of an electrical insulator should be such that the decrease of flash over distance is minimum when the insulator is wet. That is why the upper most petticoat of a pin insulator has umbrella type designed so that it can protect, the rest lower part of the insulator from rain. The upper surface of top most petticoat is inclined as less as possible to maintain maximum flash over voltage during raining. 2. To keep the inner side of the insulator dry, the rain sheds are made in order that these rain sheds should not disturb the voltage distribution they are so designed that their subsurface at right angle to the electromagnetic lines of force.

Post Insulator

post insulator Post insulator is more or less similar to Pin insulator but former is suitable for higher voltage application. Post insulator has higher numbers of petticoats and has greater height. This type of insulator can be mounted on supporting structure horizontally as well as vertically. The insulator is made of one piece of porcelain but has fixing clamp arrangement are in both top and bottom end. The main differences between pin insulator and post insulator are,
SLPin InsulatorPost Insulator
1It is generally used up to 33KV systemIt is suitable for lower voltage and also for higher voltage
2It is single stag It can be single stag as well as multiple stags
3Conductor is fixed on the top of the insulator by binding Conductor is fixed on the top of the insulator with help of connector clamp
4Two insulators cannot be fixed together for higher voltage applicationTwo or more insulators can be fixed together one above other for higher voltage application
4Metallic fixing arrangement provided only on bottom end of the insulatorMetallic fixing arrangement provided on both top and bottom ends of the insulator

Suspension Insulator

suspension insulator In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator because size, weight of the insulator become more. Handling and replacing bigger size single unit insulator are quite difficult task. For overcoming these difficulties, suspension insulator was developed. In suspension insulator numbers of insulators are connected in series to form a string and the line conductor is carried by the bottom most insulator. Each insulator of a suspension string is called disc insulator because of their disc like shape.

Advantages of Suspension Insulator

1. Each suspension disc is designed for normal voltage rating 11KV(Higher voltage rating 15KV), so by using different numbers of discs, a suspension string can be made suitable for any voltage level.
2. If any one of the disc insulators in a suspension string is damaged, it can be replaced much easily.
3. Mechanical stresses on the suspension insulator is less since the line hanged on a flexible suspension string.
suspension string 4. As the current carrying conductors are suspended from supporting structure by suspension string, the height of the conductor position is always less than the total height of the supporting structure. Therefore, the conductors may be safe from lightening.

Disadvantages of Suspension Insulator

1. Suspension insulator string costlier than pin and post type insulator.
2. Suspension string requires more height of supporting structure than that for pin or post insulator to maintain same ground clearance of current conductor.
3. The amplitude of free swing of conductors is larger in suspension insulator system, hence, more spacing between conductors should be provided.

Strain Insulator

When suspension string is used to sustain extraordinary tensile load of conductor it is referred as string insulator. When there is a dead end or there is a sharp corner in transmission line, the line has to sustain a great tensile load of conductor or strain. A strain insulator must have considerable mechanical strength as well as the necessary electrical insulating properties. strain insulator

Rated System VoltageNumber of disc insulator used in strain type tension insulator stringNumber of disc insulator used in suspension insulator string
33KV 33
66KV 54
132KV 98
220KV 1514

Stay Insulator

stay insulator

For low voltage lines, the stays are to be insulated from ground at a height. The insulator used in the stay wire is called as the stay insulator and is usually of porcelain and is so designed that in case of breakage of the insulator the guy-wire will not fall to the ground. shackle insulator or spool insulator

Shackle Insulator or Spool Insulator

The shackle insulator or spool insulator is usually used in low voltage distribution network. It can be used both in horizontal and vertical position. The use of such insulator has decreased recently after increasing the using of underground cable for distribution purpose. The tapered hole of the spool insulator distributes the load more evenly and minimizes the possibility of breakage when heavily loaded. The conductor in the groove of shackle insulator is fixed with the help of soft binding wire.

Tuesday, 14 April 2015

Light Emitting Elements And Their Types

INTRODUCTION

The use and application of light cannot be overemphasized. Our natural source of light being an electromagnetic radiation that reaches us from the sun. Without that radiation, no life would remain on this planet.
The ultraviolet ray reaching us from the sun is trapped by the green plants. They make use of it to manufacture their own food which we in turn consume. In the stone ages, men lit fire to enhance their vision at night. As time swiftly went by, man began to amaze the body of knowledge as new discoveries were made.
Man soon thought of how to artificially generate light. Inventions were made and it’s still improving. From light emitting elements that consumed a lot of energy, dissipating most of it in form of heat while a minute fraction of it is converted to light to a modern light emitting devices that consumes less energy, less heat production and with more efficiency. Thomas Edison did a very good job and credit goes to him for inventing the fluorescent Bob.
How is light energy generated from electricity? Before we talk about that, let’s check out some few things first so as to have a better understanding.Light Emitting Elements And Their Types

HEAT FROM ELECTRICITY

Electricity produces heat. The heat produced (in case) of the flow of electric current through a conductor containing impurities that opposes the flow of current. The free movement of electrons between atoms in a lattice along a conducting wire constitutes heat.
During movement, electrons collide with each other and with the atoms, hence heat is produced in the process. Resistance of a conducting wire is also a factor that constitutes to the heat a conducting wire produces. Let the Heat produced during conduction is designated by H.
It is proportional to the resistance R of the conductor and proportional to the time (t) for the current to flow through the conductor and also proportional to the square of the current. Hence if the constant k of proportionality is 1,
H = I2Rt.

it is also known as Joule’s Law.

HEATING EFFECT OF ELECTRIC CURRENT

When high current is passed through a conductor, the resultant is an immense heat production. The collision of electrons occurs frequently and causes an increase in the internal energy of the atoms thereby making the electrons to vibrate because of the heat energy acquired. At high temperature, some wires glow.
All the electrical energy is converted to heat. At low current and temperature, the conducting wire will not glow due to the lack of sufficient energy needed to excite the electrons to jump from one energy level to the other which will lead to the production of light in the process.

LIGHT FROM ELECTRICITY

From our discussion above, we can tell that electricity can be converted to light energy. When we turn on our home switch, light turns on, the electric bobs converts electrical energy to light energy.
The light comes from the heating effect of electricity. Devices that converts electricity into light was discovered long ago and since then have been improved. The early devices had very low efficiency in that it consumed a lot of energy.
The bad side of the early devices consumed a lot of heat and converts only the minute fraction of the energy it consumes into light. Today there are electric bobs that have high efficiency compared to the early ones. They consume less energy and convert most of the energy to light.
Below are some electrical elements that convert electricity into light with their mode of operation.

FILAMENT LAMP:

a filament lamp glows white hot. At high temperature, part of the electrical energy is converted into light energy while the rest is converted to heat energy. In a filament lamp, tungsten filament is enclosed in a glass. Earlier lamps used carbon as a filament which also has high melting point.
The original tungsten lamp had a vacuum inside the envelope to prevent the oxidation of the tungsten at high temperature. Modern lamps are prevented from evaporation by filling it with argon. The quartz-iodine lamp produces light of high intensity.
The envelope is made of quartz which can stand high temperature without melting. The tungsten filament lamp converts only 7% of the energy it receives into light and the rest will be converted to heat.
FILAMENT LAMP
Filament Lamp (Bulb)

DISCHARGE LAMP:

discharge lamps are with sodium vapor, neon gas, mercury vapor etc. Sodium and mercury vapor gives yellow light and are used in street lighting. Electrical discharge is passed through the gases.
When the gases absorb energy, they become excited. The atoms emit light in the red region when they become excited. The lamps that indicates when a main socket is switched on is generally a small neon lamp. Neon discharge tubes can have different shapes and are also used in advertising display.
Discharge Lamp
Discharge Lamp

FLUORESCENT LAMP:

Fluorescent lamps are widely used in offices, factories, shops etc because of its efficiency. Its efficiency is about three times the efficiency of the filament lamp. Its heat production is low. You can easily tell that by holding the lamp after minutes of turning on of the lamp. It contains mercury vapor and argon.
During discharge, mercury vapor emits light of considerable wavelength including the ultraviolet radiation. The inner surface of the tube is coated with fluorescent material to absorb the ultraviolet (UV) radiation and emits the absorbed energy in the form of visible light.
FLUORESCENT LAMP
FLUORESCENT LAMP

LIGHT EMITTING DIODE (LED):

Diodes are semiconductors. Some of them emit light when their atoms become excited due to the electrical energy they receive. They are small in size, some even less than 1mm in diameter. They are often used as indicator lamps. They have long life span and is not easily broken. The illuminated figures in pocket calculators, digital watches and digital clocks are usually made from LED.
Each digit consists of seven bar-shaped diodes arranged in a pattern similar to figure eight. Groups of diode are lit to form any figure, letters of the alphabet. Its advantage is that they lit up in a very short (they don’t require warming) and goes dark easily when they are cut off from power supply.
LIGHT EMITTING DIODE (LED)
LIGHT EMITTING DIODE (LED)
To cut down your electricity bill, avoid using lamps that consumes too much energy. Don’t think by turning off the other appliances and leaving the lamps on, electricity bills won’t pile up. Use lamps that consume less energy like the fluorescent lamps and if necessary that you use the filament lamps, turn it off after use.

CPDWD GENERAL SPECIFICATION FOR ELECTRICAL WORKS

Thursday, 9 April 2015

Complete overview of lightning arresters

Complete overview of lightning arresters 

Complete overview of lighting arresters
Top

Lightning and Voltage Surge

Rod arrester
Rod arrester
Lightning can create voltage surges in several of the following ways. Lightning can score a direct hit on your house. It can strike the overhead power line which enters your house, or a main power line that is blocks away from your home. Lightning can strike branch circuitry wiring in the walls of your house.
Lightning can strike an object near your home such as a tree or the ground itself and cause a surge. Voltage surgescan be created by cloud to cloud lightning near your home. A highly charged cloud which passes over your home can also induce a voltage surge.
Voltage surges can also be caused by standard on and off switching activities of large electric motors or pieces of equipment. These surges can be created by a neighbor, or by a business or manufacturing facility some distance from your house. These surges are insidious and for the most part are silent.
They can occur with little or no warning.
Top

Methodology to Suppress Lighting and Voltage Surge:

When a voltage surge is created, it wants to equalize itself and it wants to do it as quickly as possible. These things seem to have very little patience. The surges will do whatever it takes to equalize or neutralize themselves, even if it means short circuiting all of your electronic equipment.
The method of providing maximum protection for equipment is quite simple. Create a pathway for the voltage surge (electricity) to get to and into the ground outside your house as quickly as possible.
This is not, in most cases, a difficult task.
The first step is simple. Create an excellent grounding system for your household electrical system. The vast majority of homes do not have an excellent grounding system. Many homes have a single grounding rod and /or a metallic underground water pipe which are part of the electrical grounding system. In most cases, this is inadequate. The reason is somewhat easy to explain. Imagine putting a two inch fire hose into your kitchen sink and opening the nozzle to the full on position. I doubt that the drain in your sink could handle all of the water. Your grounding system would react in the same way to a massive voltage surge. Just as the water jumps out of the sink, the electricity jumps from the grounding system and looks for places to go. Frequently it looks for the microchips in your electronic devices. They are an easy target. They offer a path of least resistance.
Voltage surges want to be directed to the grounding system, and when they do, they want to get into the ground around your house in a hurry. You can achieve this by driving numerous grounding rods into virgin soil around your house. These rods should be UL approved and connected by a continuous heavy solid copper wire which is welded to each grounding rod. This solid copper wire begins on the grounding bar inside of your electrical panel and terminates at the last grounding rod. Avoid using clamps if at all possible. Over time, the connection at the clamp can corrode or become loose creating tremendous resistance. This will act as a roadblock to the electricity trying to get into the ground around your home.
The grounding rods should be at least ten feet apart from one another. They should be located in soil which readily accepts electricity. Moist clay soils are very desirable. Rocky, sandy, or soils with gravel generally have high resistance factors. Electricity has a tough time dissipating into them. Resistance readings should be in the range of 10 to 30 ohms. The lower the better.
The second step in household surge protection is to install a lightning arrester inside of your electric service panel. These devices can be extremely effective in intercepting large voltage surges which travel in the electric power lines. These devices capture the voltage surges and ‘bleed’ them off to the grounding wire which we just spoke of. If for some reason you do not have a large enough grounding wire, or enough ground rods, the arrester cannot do its job. It must be able to send the surge quickly to the ground outside of your house. These arresters range in price from $50.00 to $175.00. Almost every manufacturer of circuit breakers makes one to fit inside their panel. They can be installed by a homeowner who is experienced in dealing with high voltage panels. If you do not have this capability, have an experienced electrician install it for you.
The final step in the protection plan is to install ‘point of use’ surge suppression devices. Often you will see these called ‘transient voltage surge suppressors’. These are your last line of defense. They are capable of only stopping the leftover voltage surge which got past the grounding system and the lightning arrester. They cannot protect your electronic devices by themselves. They must be used in conjunction with the grounding system and the lightning arresters. Do not be lulled into a false sense of security if you merely use one of these devices!
The ‘point of use’ surge suppression devices are available in various levels of quality.Some are much better than others. What sets them apart are several things. Generally speaking, you look to see how fast their response time is. This is often referred to as clamping speed. Also, look to see how high of a voltage surge they will suppress. Make sure that the device has a 500 volt maximum UL rated suppression level. Check to see if it has an indicator, either visual or audio, which lets you know if it is not working. The better units offer both, in case you install the device out of sight. Check to see if it offers a variety of modes with respect to protection. For example, does the device offer protection for surges which occur between the ‘hot’ and neutral, between ‘hot’ and ground, as well as between neutral and ground. There is a difference! Check to see if it monitors the normal sine waves of regular household current. Surges can cause irregularities in these wave patterns. Good transient surge suppression devices ‘devour’ these voltage spikes. Finally, check the joule rating. Attempt to locate a device which has a joule rating of 140 or higher. Electrical supply houses often are the best place to look for these high quality devices.
Some devices can also protect your phone equipment at the same time. This is very important for those individuals who have computer modems. Massive voltage surges can come across phone lines as well. These surges can enter your computer through the telephone line! Don’t forget to protect this line as well. Also, be sure the telephone ground wire is tied to the upgraded electrical grounding system.

Complete overview of lightning arresters (part 2)

Complete overview of lighting arresters
Top
Continued from article Complete overview of lightning arresters (part 1)

What is a surge arrester?

Surge arresters are devices that help prevent damage to apparatus due to high voltages. The arrester provides a low-impedance path to ground for the current from a lightning strike or transient voltage and then restores to a normal operating conditions.
A surge arrester may be compared to a relief valve on a boiler or hot water heater. It will release high pressure until a normal operating condition is reached. When the pressure is returned to normal, the safety valve is ready for the next operation.
When a high voltage (greater than the normal line voltage) exists on the line, the arrester immediately furnishes a path to ground and thus limits and drains off the excess voltage. The arrester must provide this relief and then prevent any further flow of current to ground. The arrester has two functions; it must provide a point in the circuit at which an over-voltage pulse can pass to ground and second, to prevent any follow-up current from flowing to ground.
Top

Causes of over voltages

  • Internal causes
  • External causes

Internal causes

Switching surge

The overvoltages produced on the power system due to switching are known as switching surge.

Insulation failure

The most common case of insulation failure in a power system is the grounding of conductors (i.e. insulation failure between line and earth) which may cause overvoltage in the system.

Arcing ground

The phenomenon of intermittent arc taking place in line to ground fault of a 3phase system with consequent production of transients is known as arcing ground.

Resonance

It occurs in an electrical system when inductive reactance of the circuit becomes equal to capacitive reactance. under resonance , the impedance of the circuit is equal to resistance of the circuit and the p.f is unity.
Top

Types of lightning strokes

  1. Direct stroke
  2. Indirect stroke

(1) Direct stroke

In direct stroke, the lightning discharge is directly from the cloud to the subject equipment. From the line, the current path may be over the insulator down the pole to the ground.

(2) Indirect stroke

Indirect stroke results from the electro statically induced charges on the conductors due to the presence of charge clouds.
Top

Harmful effects of lightning

The traveling waves produced due to lightning will shatter the insulators. If the traveling waves hit the windings of a transformer or generator it may cause considerable damage.

Protection against lightning

Different types of protective devices are:
  1. Earthing screen
  2. Overhead ground wires
  3. Lightning arresters

(1) The Earthing screen

The power station & sub-station can be protected against direct lightning strokes by providing earthing screens. On occurrence of direct stroke on the station ,screen provides a low resistance path by which lightning surges are conducted to ground.
Limitations: It does not provide protection against the traveling waves which may reach the equipments in the station.

(2) Overhead ground wires

It is the most effective way of providing protection to transmission lines against direct lightning strokes. It provides damping effect on any disturbance traveling along the lines as it acts as a short-circuited secondary.
Limitations:
  • It requires additional cost.
  • There is a possibility of its breaking and falling across the line conductors, thereby causing a short-circuit fault.

(3) Lightning Arresters

It is a protective device which conducts the high voltage surge on the power system to ground. The earthing screen and ground wires fail to provide protection against traveling waves. The lightning arrester provides protection against surges.
Top

AC Power Surge Arrester

Type 1 Surge Protectors

Type 1 surge protectors are designed to be installed where a direct lightning strike risk is high, especially when the building is equipped with external lightning protection system (LPS or lightning rod).
In this situation IEC 61643-11 standards require the Class I test to be applied to surge protectors : this test is characterized by the injection of 10/350 μs impulse current in order to simulate the direct lightning strike consequence. Therefore these Type 1 surge protectors must be especially powerful to conduct this high energy impulse current.

Type 2 surge protectors

Type 2 surge protectors are designed to be installed at the beginning of the installation, in the main switchboard, or close to sensitive terminals, on installations without LPS (lightning rods). These protectors are tested following the Class II test from IEC61643-11 based on 8/20 μs impulse current injection.

Type 3 surge protectors

In case of very sensitive or remote equipment, secondary stage of surge protectors is required : these low energy SPDs could be Type 2 or Type 3. Type 3 SPDs are tested with a combination waveform (1,2/50 μs – 8/20 μs) following Class III test.

Types of Lightning Arrestors according to Class

1. Station Class

  • Station class arrestors are typically used in electrical power stations or substations and other high voltage structures and areas.
  • These arrestors protect against both lightning and over-voltages, when the electrical device has more current in the system than it is designed to handle.
  • These arrestors are designed to protect equipment above the 20 mVA range.

2. Intermediate Class

  • Like station class arrestors, intermediate class arrestors protect against surges from lightning and over-voltages, but are designed to be used in medium voltage equipment areas, such as electrical utility stations, substations, transformers or other substation equipment.
  • These arrestors are designed for use on equipment in the range of 1 to 20 mVA.

3. Distribution Class

  • Distribution class arrestors are most commonly found on transformers, both dry-type and liquid-filled.
  • These arrestors are found on equipment rated at 1000 kVA or less.
  • These arrestors are sometimes found on exposed lines that have direct connections to rotating machines.

4. Secondary Class

  • Secondary class lightning arrestors are designed to protect most homes and businesses from lightning strikes, and are required by most electrical codes, according to, Inc., an electrical power protection company.
  • These arrestors cause high voltage overages to ground, though they do not short all the over voltage from a surge. Secondary class arrestors offer the least amount of protection to electrical systems, and typically do not protect solid state technology, or anything that has a microprocessor.
Top

Choosing the right AC Power Surge Arrester

AC power surge protectors is designed to cover all possible configurations in low voltage installations. They are available in many versions, which differ in:
  • Type or test class (1 , 2 or 3)
  • Operating voltage (Uc)
  • AC network configuration (Single/3-Phase)
  • Discharge currents (Iimp, Imax, In)
  • Protection level (Up)
  • Protection technology (varistors, gas tube-varistor, filter)
  • Features (redundancy, differential mode, plug-in, remote signaling…).
The surge protection selection must be done following the local electrical code requirements (i.e. minimum rating for In) and specific conditions (i.e. high lightning density).
Top

Working Principle of Lightning Arrester

The earthing screen and ground wires can well protect the electrical system against direct lightning strokes but they fail to provide protection against traveling waves, which may reach the terminal apparatus. The lightning arresters or surge diverts provide protection against such surges. A lightning arrester or a surge diverted is a protective device, which conducts the high voltage surges on the power system to the ground.
The earthing screen and ground wires can well protect the electrical system against direct lightning strokes but they fail to provide protection against traveling waves, which may reach the terminal apparatus. The lightning arresters or surge diverters provide protection against such surges. A lightning arrester or a surge diverted is a protective device, which conducts the high voltage surges on the power system to the ground.
Fig below shows the basic form of a surge diverter.
Basic form of a surge diverter
Basic form of a surge diverter

It consists of a spark gap in series with a non-linear resistor. One end of the diverter is connected to the terminal of the equipment to be protected and the other end is effectively grounded. The length of the gap is so set that normal voltage is not enough to cause an arc but a dangerously high voltage will break down the air insulation and form an arc. The property of the non-linear resistance is that its resistance increases as the voltage (or current) increases and vice-versa.
This is clear from the volt/amp characteristic of the resistor shown in Figure above.
The action of the lightning arrester or surge diverter is as under:
  1. Under normal operation, the lightning arrester is off the line i.e. it conducts no current to earth or the gap is non-conducting
  2. On the occurrence of over voltage, the air insulation across the gap breaks down and an arc is formed providing a low resistance path for the surge to the ground. In this way, the excess charge on the line due to the surge is harmlessly conducted through the arrester to the ground instead of being sent back over the line.
  3. It is worthwhile to mention the function of non-linear resistor in the operation of arrester. As the gap sparks over due to over voltage, the arc would be a short-circuit on the power system and may cause power-follow current in the arrester. Since the characteristic of the resistor is to offer low resistance to high voltage (or current), it gives the effect of short-circuit. After the surge is over, the resistor offers high resistance to make the gap non-conducting.
courtesy- Mr.Jignesh Parmar